How large industrial chiller is suitable for the machine?

How to choose the industrial chiller that Zui is suitable for, in fact, it is very simple to have a selection formula:
Cooling capacity = chilled water flow * 4.187 * temperature difference * coefficient
1. The chilled water flow refers to the cold water flow required for the operation of the machine, and the unit needs to be converted into liters per second;
2. The temperature difference refers to the temperature difference between the inlet and outlet of the machine;
3. 4.187 is quantitative (specific heat capacity of water);
4. When choosing an air-cooled chiller, multiply the factor by 1.3, and select a water-cooled chiller to multiply by a factor of 1.1.
5. Select the appropriate machine model based on the calculated cooling capacity.
It is customary to use the P to calculate how much the chiller should be equipped with, but the main thing is to know the rated cooling capacity. If the air-cooled 9.07KW is used, choose a 3P machine. And so on. Therefore, the choice of industrial chiller is important to determine the rated cooling capacity.